@@ -140,6 +140,14 @@ PMP_SS_RMM: | |||
- low_pressure_status | |||
- high_pressure_status | |||
|
|||
PMP_CPVSC2X_WDPC: |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
The entity type should refer to a single PMP
, not a collection of two. Points like CPVSC2X
would be used on a boiler or system.
- heater_run_status_1 | ||
- heater_run_status_2 | ||
- heater_run_status_3 | ||
- failed_alarm_1 |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Make alarms optional.
@@ -3110,3 +3110,7 @@ literals: | |||
- ultraviolet_irradiance_sensor: | |||
fixed_min: 0.0 | |||
flexible_max: 2000.0 | |||
|
|||
- heating_water_temperature_setpoint: |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
See above comment. Setpoint should not be on the tank itself. You should be able to use supply_water_temperature_setpoint
or similar on the system instead.
No description provided.